EPA 608 Type II Practice Test: 25 Original Questions

Updated

0 of 25 answered, 0 correct

Next unanswered
  1. Which of these jobs calls for Type II certification under 40 CFR 82.161(a)(1)(ii)?
    Show the answer

    B. Servicing a high-pressure appliance other than a small appliance, an MVAC or an MVAC-like one

    Type II covers medium-, high- and very-high-pressure appliances, apart from small appliances, MVACs and MVAC-like appliances. Small appliances are Type I work (and disposing of one, or of an MVAC or MVAC-like appliance, needs no certification), and low-pressure appliances are Type III. 40 CFR 82.161(a)(1)(ii): “Persons who maintain, service, repair, or dispose of medium-, high-, or very high-pressure appliances (except small appliances, MVACs, and MVAC-like appliances) must be certified as Type II technicians.”

    Source: 40 CFR 82.161(a)(1)(ii)

  2. A technician services MVAC-like appliances. Which certification does 40 CFR 82.161 accept for that work?
    Show the answer

    C. Either Type II, or certification under 40 CFR part 82, subpart B

    Servicing MVAC-like appliances can be covered either way: Type II, or the MVAC certification in subpart B. Only disposing of them needs no certification. 40 CFR 82.161(a)(1)(v): “Technicians who maintain, service, or repair MVAC-like appliances must either be certified as Type II technicians or be certified in accordance with 40 CFR part 82, subpart B”.

    Source: 40 CFR 82.161(a)(1)(v)

  3. What kind of test must a technician pass to be certified as Type II?
    Show the answer

    A. A closed-book, proctored test given in a secure environment by an EPA-approved certifying program

    Only Type I programs may use the mail-in format. Type II and Type III need a closed-book, proctored test, and proctors must make sure no notes or training materials are used. Appendix D, section a: “Technicians must pass a closed-book, proctored test, administered in a secure environment, by an EPA-approved certifying program to be certified as a Type II or Type III technician.”

    Source: 40 CFR Part 82, Subpart F, Appendix D, section a (Test Preparation)

  4. When people take certification tests at the same time at one site, how many registered proctors must the certifying program designate?
    Show the answer

    D. At least one for every 50 people

    Appendix D ties the number of proctors to the number testing at once: one for every 50. 25 and 100 are question counts, not proctor ratios. Appendix D, section b: programs must “designate at least one proctor registered for every 50 people taking tests at the same time at a given site”.

    Source: 40 CFR Part 82, Subpart F, Appendix D, section b (Proctoring)

  5. The Type II part of the test is drawn from Group II. What kind of questions does Appendix D say Group II asks?
    Show the answer

    C. Sector-specific questions, in areas such as leak detection, recovery techniques, safety, shipping and disposal

    Group II is split by sector (Type I, Type II and Type III) and covers leak detection, recovery techniques, safety, shipping and disposal. Laws and regulations and environmental impact are Group I, core areas. Appendix D, section d: “Group II will ask questions covering sector-specific” issues in those five areas.

    Source: 40 CFR Part 82, Subpart F, Appendix D, section d (Test Content)

  6. Under 40 CFR 82.157 as it reads today, which appliance must follow the Section 608 leak-repair requirements?
    Show the answer

    A. A comfort-cooling appliance holding 60 pounds of R-22

    Since April 10, 2020, Section 608 leak repair covers only large appliances using class I or class II refrigerant. R-22 is HCFC-22, which Appendix B to Subpart A of 40 CFR Part 82 lists as a class II controlled substance. 30 pounds is under the threshold, and 15 pounds is the separate 2024 HFC rule's figure. 40 CFR 82.157(a): “As of April 10, 2020, this section applies only to appliances with a full charge of 50 or more pounds of any class I or class II refrigerant or blend containing a class I or class II refrigerant.”

    Source: 40 CFR 82.157(a)

  7. A 200-pound comfort-cooling appliance holds only a substitute refrigerant. Does 40 CFR 82.157 apply to it?
    Show the answer

    C. No, because 82.157 doesn't apply to appliances containing solely substitute refrigerants

    Section 608 leak repair now reaches only appliances using class I or class II refrigerant, so the charge size doesn't bring this one in. A substitute-only appliance may fall under the separate 2024 HFC rule instead, which is where the January 1, 2026 date comes from. 40 CFR 82.157(a): “the requirements of this section do not apply to appliances containing solely substitute refrigerants.”

    Source: 40 CFR 82.157(a)

  8. Unless a paragraph of 40 CFR 82.157 says otherwise, whom do its requirements apply to?
    Show the answer

    B. The owner or operator of the appliance

    The leak-repair duties sit with the appliance's owner or operator unless a paragraph names someone else. Technicians, distributors and manufacturers aren't the default. 40 CFR 82.157(a): “Unless otherwise specified, the requirements of this section apply to the owner or operator of the appliance.”

    Source: 40 CFR 82.157(a)

  9. A technician adds refrigerant to an appliance covered by 40 CFR 82.157. What must the technician do when the service is finished?
    Show the answer

    D. Give the owner or operator documentation that meets the rule's requirements

    Whoever adds or removes refrigerant hands documentation to the owner or operator at the end of the job. Nothing in 82.157(b) sends it to EPA or makes the technician fix every leak on the spot. 40 CFR 82.157(b): “Persons adding or removing refrigerant from an appliance must, upon conclusion of that service, provide the owner or operator with documentation”.

    Source: 40 CFR 82.157(b)

  10. How often must the owner or operator of an appliance covered by 40 CFR 82.157 calculate its leak rate?
    Show the answer

    A. Every time refrigerant is added, apart from the exceptions the rule lists

    The calculation is tied to each refrigerant addition, not to a calendar or a technician's report. 40 CFR 82.157(b): “The owner or operator must calculate the leak rate every time refrigerant is added to an appliance”, with a short list of exceptions.

    Source: 40 CFR 82.157(b)

  11. A commercial refrigeration appliance is covered by 40 CFR 82.157. Above what leak rate must its owner repair leaks?
    Show the answer

    C. 20 percent

    Commercial refrigeration equipment has its own threshold in 82.157(c)(2). The other percentages either belong to other appliance categories or aren't leak rates in the rule. 40 CFR 82.157(c)(2)(i): “20 percent leak rate for commercial refrigeration equipment”.

    Source: 40 CFR 82.157(c)(2)

  12. Which leak rate does 40 CFR 82.157 set for industrial process refrigeration equipment?
    Show the answer

    A. 30 percent

    Industrial process refrigeration gets the highest threshold in 82.157(c)(2). 50 percent isn't a rate in the rule, and the lower figures belong to other appliance categories. 40 CFR 82.157(c)(2)(ii): “30 percent leak rate for industrial process refrigeration equipment”.

    Source: 40 CFR 82.157(c)(2)

  13. An office building's comfort-cooling appliance is covered by 40 CFR 82.157. Which leak rate applies to it?
    Show the answer

    B. 10 percent

    Comfort cooling shares the lowest threshold with other covered appliances outside the commercial and industrial process categories. The higher figures belong to those two categories, and 15 percent isn't a rate in the rule. 40 CFR 82.157(c)(2)(iii): “10 percent leak rate for comfort cooling appliances or other appliances with a full charge of 50 or more pounds of refrigerant”.

    Source: 40 CFR 82.157(c)(2)

  14. Refrigerant is added to a covered appliance whose leak rate is over its threshold, and no industrial process shutdown is needed. How long does 40 CFR 82.157(d) allow to identify and repair the leaks?
    Show the answer

    B. 30 days

    The standard deadline is 30 days from the refrigerant addition. The longer 120-day window applies only when an industrial process shutdown is required. 40 CFR 82.157(d): leaks must be identified and repaired “within 30 days (or 120 days if an industrial process shutdown is required)” of that addition.

    Source: 40 CFR 82.157(d)

  15. An owner chose to repair a covered appliance but couldn't bring its leak rate below the threshold. What does 40 CFR 82.157(c)(1) require next?
    Show the answer

    C. Create and implement a retrofit or retirement plan

    When repair fails, the owner or operator moves to a retrofit or retirement plan under paragraphs (h) and (i). The rule offers no route that keeps a leaking appliance running on top-offs or a penalty. 40 CFR 82.157(c)(1): “the owner or operator must create and implement a retrofit or retirement plan”.

    Source: 40 CFR 82.157(c)(1)

  16. EPA's fact sheet on its 2024 HFC rule sets out which appliances its leak-repair provisions reach. Which charge and refrigerant bring an appliance in?
    Show the answer

    B. 15 pounds or more of a refrigerant that contains an HFC or an HFC substitute with a GWP greater than 53

    The 2024 rule starts at 15 pounds and reaches HFCs and their substitutes above GWP 53, with compliance from January 1, 2026. 50 pounds of class I or class II refrigerant is the Section 608 threshold in 82.157. Fact sheet, Table 1: appliances “with a full charge of 15 pounds or more of a refrigerant that contains an HFC or a substitute for an HFC with a GWP greater than 53”.

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Table 1: Leak Repair

  17. According to EPA's fact sheet, which of these appliances does the 2024 HFC leak-repair rule leave out?
    Show the answer

    D. Residential and light-commercial air conditioners and heat pumps

    A footnote to Table 1 takes the residential and light-commercial air conditioning and heat pump sector out of the leak-repair provisions. Commercial refrigeration, industrial process refrigeration and comfort cooling all have leak-rate thresholds in that table. Fact sheet, Table 1, note b: “Appliances in the residential and light commercial air conditioning and heat pumps sector are not included in these provisions.”

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Table 1: Leak Repair

  18. A technician takes the Type II certification test. By when must the certifying program tell the technician the result?
    Show the answer

    C. Within 30 days of the test

    Appendix D gives certifying programs 30 days from the test date to report results. 7, 60 and 90 days don't appear in the grading rule. Appendix D, section e: “Certifying programs must inform the applicant of their test results no later than 30 days from the date of the test.”

    Source: 40 CFR Part 82, Subpart F, Appendix D, section e (Grading)

  19. Where in the Code of Federal Regulations are the full requirements of EPA's 2024 HFC leak-repair program?
    Show the answer

    B. 40 CFR Part 84, subpart C

    EPA's fact sheet points to Part 84, subpart C. 82.157 now covers only class I and class II refrigerants, subpart B of Part 82 is where MVAC technician certification sits, and Part 266, subpart Q holds the RCRA alternative standards. Fact sheet: “Refer to 40 CFR part 84 subpart C for full requirements.”

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Key provisions

  20. Under EPA's 2024 HFC rule, which new commercial or industrial process refrigeration appliances containing an HFC must install and use automatic leak detection?
    Show the answer

    D. Those with a full charge of 1,500 pounds or more

    Automatic leak detection is kept for the largest systems. 15 pounds is where the rule's leak-repair provisions start, 50 pounds is the Section 608 leak-repair threshold, and 500 pounds isn't a figure in Table 2, which sets 1,500 pounds for both new and existing appliances. Fact sheet, Table 2: appliances installed with a “full charge size of 1,500 pounds or more”.

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Table 2: Automatic Leak Detection

  21. Under EPA's 2024 HFC rule, how much virgin HFC may reclaimed HFC refrigerant contain?
    Show the answer

    A. No more than 15%, by weight

    Reclaimed HFC refrigerant may carry at most 15 percent virgin HFC by weight, and it must be labeled. 20 percent is a leak-rate figure, not a reclaim limit. Fact sheet, Table 3: “Reclaimed HFC refrigerants can contain no more than 15%”, by weight, of virgin HFCs.

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Table 3: Reclaimed HFCs

  22. Under the 2024 HFC rule's alternative method for disposable cylinders, to what vacuum does a Section 608 certified technician evacuate the cylinder before it goes to the final processor?
    Show the answer

    C. 15 in-Hg

    The alternative method, from January 1, 2028, is a 15 in-Hg vacuum plus a certification statement given to the final processor. The other levels aren't part of the disposable-cylinder provision. Fact sheet, Table 5: a certified technician “evacuates a disposable cylinder to a vacuum level of 15 in-Hg”.

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Table 5: Disposable Cylinders

  23. Under EPA's RCRA alternative standards, what must a reclaimer that receives ignitable spent refrigerant from off-site for recycling maintain?
    Show the answer

    B. EPA Clean Air Act section 608 certification

    The reclaimer keeps its Section 608 certification, and the facility must also meet emergency preparedness and response requirements. Table 6 asks for no per-employee technician certificates. Fact sheet, Table 6: “The reclaimer must maintain EPA CAA section 608 certification”.

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Table 6: RCRA Alternative Standards

  24. Which of these refrigerant additions does 40 CFR 82.157(b) name as an exception to the leak-rate calculation?
    Show the answer

    D. An addition made immediately following a retrofit

    Three additions are excused: one made right after a retrofit, one made on installing a new appliance, and one that qualifies as a seasonal variance. The rule has no small-quantity, calendar or who-did-it exception. 40 CFR 82.157(b): the calculation is required “unless the addition is made immediately following a retrofit, installation of a new appliance, or qualifies as a seasonal variance”.

    Source: 40 CFR 82.157(b)

  25. A store's commercial refrigeration appliance holds 25 pounds of a refrigerant that contains an HFC and has a GWP greater than 53. It holds no class I or class II refrigerant. Which leak-repair rule covers it, and at what leak rate?
    Show the answer

    B. The 2024 HFC rule, at 20%

    The appliance is over the HFC rule's 15-pound threshold, its refrigerant is above GWP 53, and it isn't residential or light-commercial air conditioning, so the 2024 rule applies at the commercial refrigeration rate. 82.157 doesn't reach it: it holds no class I or class II refrigerant and is under 50 pounds. 10% is the comfort-cooling rate. Fact sheet, Table 1: “Commercial refrigeration: 20%”.

    Source: EPA ER&R Program fact sheet (Sept. 20, 2024), Table 1: Leak Repair

Answered 0 of 25: 0 correct so far.

Get new EPA 608 practice tests by email

Leave your email and we'll tell you when we add more EPA 608 practice tests and questions. Nothing else.

25 original Type II questions on who needs Type II, Section 608 leak repair (now class I and II refrigerants only) and the separate 2024 HFC leak-repair rule, each cited to 40 CFR or EPA. The pass mark on a closed-book test is 70%.

Type II is the Section 608 certification for medium-, high- and very-high-pressure equipment. Here is the rule's own wording, from 40 CFR 82.161(a)(1)(ii): "Persons who maintain, service, repair, or dispose of medium-, high-, or very high-pressure appliances (except small appliances, MVACs, and MVAC-like appliances) must be certified as Type II technicians."

The 25 questions below are original. They were written from the regulation and from EPA's 2024 fact sheet, not lifted from any exam. The Type II test is closed-book, and its pass mark of 70% comes to 18 of 25 on this set. Choose an answer and the question locks, then shows whether you were right along with the source paragraph. Your answers never leave the browser.

Worked example: which leak-repair rule applies?

Show the math

Picture two comfort-cooling appliances, each with a full charge of 60 pounds. One runs on R-22. The other holds nothing but a substitute refrigerant.

Start with Section 608. Paragraph (a) of 82.157 draws the boundary: "As of April 10, 2020, this section applies only to appliances with a full charge of 50 or more pounds of any class I or class II refrigerant or blend containing a class I or class II refrigerant." R-22 is HCFC-22, and Appendix B to Subpart A of 40 CFR Part 82 names HCFC-22 in its table of class II controlled substances. With 60 pounds against a 50-pound line, the first appliance is inside the rule.

The same paragraph then shuts the second one out: "the requirements of this section do not apply to appliances containing solely substitute refrigerants." Of the two, only the R-22 appliance falls under 82.157.

That doesn't leave the second appliance unregulated. If its refrigerant contains an HFC, or is a substitute with a GWP above 53, its 60 pounds is four times the 15-pound line in EPA's 2024 HFC rule, covered below. The exception is equipment in the residential and light commercial air conditioning and heat pumps sector, which that rule leaves out.

Section 608 leak repair since 2020

For an appliance 82.157 still reaches, the owner or operator must work out its leak rate each time refrigerant is added. A few additions are excused, such as a charge right after installing a new appliance or a retrofit, or one that counts as a seasonal variance. The rate is then set against a limit that depends on the kind of equipment:

  • commercial refrigeration: 20%;
  • industrial process refrigeration: 30%;
  • comfort cooling, and any other appliance not in the first two groups: 10%.

If an addition shows the appliance is over its limit, the leaks have to be found and repaired within 30 days of that addition. Where the repair needs an industrial process shutdown, the window stretches to 120 days. The owner may retrofit or retire the appliance under a plan instead, and an owner who tries repairs but can't get below the limit has to move to that plan.

HFC leak repair: EPA's 2024 rule

Leaks of HFCs are handled by a separate regulation, the Emissions Reduction and Reclamation program EPA finalized in 2024 under the AIM Act. It's codified at 40 CFR Part 84, subpart C. Its leak-repair provisions apply from January 1, 2026, to appliances holding a full charge of 15 pounds or more of a refrigerant that contains an HFC, or of an HFC substitute whose GWP is above 53.

The thresholds carry the same numbers as the older rule: 30% for industrial process refrigeration, 20% for commercial refrigeration, and 10% for comfort cooling and the other appliances that neither group takes in.

A footnote to the fact sheet's leak-repair table carves out a large group: "Appliances in the residential and light commercial air conditioning and heat pumps sector are not included in these provisions." A home central air system isn't under these leak-repair provisions, however much refrigerant it holds.

Reclaim, cylinders and leak detection

The 2024 rule reaches past leak repair. Three more of its provisions, taken from the fact sheet's summary tables:

  • Reclaimed refrigerant. From January 1, 2026, reclaimed HFC refrigerant may contain no more than 15% virgin HFC, by weight.
  • Disposable cylinders. From January 1, 2028, a Section 608 certified technician may evacuate a disposable cylinder to a vacuum of 15 in-Hg and give the final processor a certification statement, instead of sending the cylinder on to have what's left removed.
  • Automatic leak detection. New commercial and industrial process refrigeration appliances with a full charge of 1,500 pounds or more of an HFC, or of a substitute with a GWP above 53, need an automatic leak detection system within 30 days of installation, starting January 1, 2026. Existing appliances of that size installed on or after January 1, 2017, and before January 1, 2026, must have one by January 1, 2027.

The fact sheet notes that its tables are for information and not for compliance. The rule text in Part 84 is what governs.

What this section doesn't cover

Appendix D lists five areas for the technical groups: leak detection, recovery techniques, safety, shipping and disposal. The regulation text saved for this site doesn't include the recovery rules, such as the required evacuation levels and the standards for recovery equipment, so none of these 25 questions tests them. Study recovery techniques, safety and shipping from your certifying organization's material before the real test.

For who needs certification and how the test is given and graded, try the Core practice test.

For how Type II fits alongside the other three certification types, see EPA 608 certification types; for a study checklist by group, see what each EPA 608 test covers.

What the 25 questions cover, and where each comes from
QuestionTopicSource
1Who needs Type II40 CFR 82.161(a)(1)(ii)
2Who needs Type II40 CFR 82.161(a)(1)(v)
3How the test works40 CFR Part 82, Subpart F, Appendix D, section a (Test Preparation)
4How the test works40 CFR Part 82, Subpart F, Appendix D, section b (Proctoring)
5How the test works40 CFR Part 82, Subpart F, Appendix D, section d (Test Content)
6Section 608 leak repair (class I and II)40 CFR 82.157(a)
7Section 608 leak repair (class I and II)40 CFR 82.157(a)
8Section 608 leak repair (class I and II)40 CFR 82.157(a)
9Section 608 leak repair (class I and II)40 CFR 82.157(b)
10Section 608 leak repair (class I and II)40 CFR 82.157(b)
11Section 608 leak repair (class I and II)40 CFR 82.157(c)(2)
12Section 608 leak repair (class I and II)40 CFR 82.157(c)(2)
13Section 608 leak repair (class I and II)40 CFR 82.157(c)(2)
14Section 608 leak repair (class I and II)40 CFR 82.157(d)
15Section 608 leak repair (class I and II)40 CFR 82.157(c)(1)
16HFC leak repair (40 CFR Part 84)EPA ER&R Program fact sheet (Sept. 20, 2024), Table 1: Leak Repair
17HFC leak repair (40 CFR Part 84)EPA ER&R Program fact sheet (Sept. 20, 2024), Table 1: Leak Repair
18How the test works40 CFR Part 82, Subpart F, Appendix D, section e (Grading)
19HFC leak repair (40 CFR Part 84)EPA ER&R Program fact sheet (Sept. 20, 2024), Key provisions
20HFC leak repair (40 CFR Part 84)EPA ER&R Program fact sheet (Sept. 20, 2024), Table 2: Automatic Leak Detection
21Reclaim and disposalEPA ER&R Program fact sheet (Sept. 20, 2024), Table 3: Reclaimed HFCs
22Reclaim and disposalEPA ER&R Program fact sheet (Sept. 20, 2024), Table 5: Disposable Cylinders
23Reclaim and disposalEPA ER&R Program fact sheet (Sept. 20, 2024), Table 6: RCRA Alternative Standards
24Section 608 leak repair (class I and II)40 CFR 82.157(b)
25HFC leak repair (40 CFR Part 84)EPA ER&R Program fact sheet (Sept. 20, 2024), Table 1: Leak Repair